8.4 Heat Pump Conguration
8.4.1 Heat Pump
"Minimum shutdown time": 0 mins... 120 mins.
"Max HP": 8°C... 100°C.
"Post-circulation": 10 secs... 600 secs...
"Power shedding operating": Automatic, When needed.
Released: HP = Start / DHW Backup = Stop / 1
st
HP Backup = Stop /
2
nd
HP Backup = Stop / Boiler = Start.
When needed (Locked): HP = Stop / DHW Backup = Stop /
1
st
HP Backup = Stop / 2
nd
HP Backup = Stop / Boiler = Start.
HP
Compressor conguration
Minimum shutdown time
8 mins
Post-circulation 240s
Max HP T° 75°C
Power shedding
operating
Released
1
- "Summer/winter switchover outd.T°" Zone 1: 8°C... 30°C.
"Mini. cooling switchover outd. T°": 8°C... 35°C.
"Mini. time prior to heat./cool.switchover ": 8h... 100h.
2
- "Circuit 2 heating": 0°C... 20°C.
- "Circuit 2 cooling": 0°C... 20°C.
1
HP
Heating/cooling conguration
Summer/winter switchover
outd.T°
18°C
Mini. cooling switchover
outd. T°
---
Mini. time prior to heat./
cool.switchover
24h
Next
2
HP
Complete
Heating/cooling conguration
Mixing valve compensation
Area 2
Area 2 heating 0°C
Area 2 cooling 0°C
"Maximum HP DHW T°": 0°C... 80°C.
"Switching dierential": 0°C... 20°C.
"Heat./cool. alternating time": 10 mins... 600 mins.
(with dynamic radiator, set to 40 mins).
HP
DHW conguration
Maximum HP DHW T°
52°C
Switching differential 7°C
Heat./cool. alternating time
90 mins
Some settings (or menus) might not be displayed. They are dependent on the installation's conguration (and installed options).
HP conguration HP
Compressor conguration
Heating/cooling conguration
DHW conguration
Installation and Operating Manual "1821- EN"
Alféa Extensa Duo A.I. Heat Pump
- 56 -