"Type of use": Power shedding + O-peak hours / Smartgrid.
"EX1: function activation": 230V / 0V.
"EX2: function activation": 230V / 0V.
Heat Pump
Tari󰀨 input conguration
EX1: function activation
230V
EX2: function activation
0V
Type of use
Power shedding +
Off-peak hours
8.4.2 Electrical back-up
"Authorisation if outd. T° <": -50°C... 50°C.
"Switching setting": 0°Cmin... 500°Cmin.
Conguration
Back-up
Switching setting
100°C min
Authorisation if outd. T° <
2°C
Some settings (or menus) might not be displayed. They are dependent on the installation's conguration (and installed options).
1
- "Authorisation if outd. T°<" : --- , -15°C... 10°C.
"Authorisation if outd. T°>" : 0°C... 30°C.
"Switching setting" : 10°C.min... 500°C.min.
2
- "Minimum shutdown time" : ---, 1min... 120min.
"Post-circulation" : 0min... 120min.
"DHW operating" : Emergency / Back-up / Priority.
1
Conguration
Connection boiler
Switching setting
Next
100°C.min
Authorisation if outd. T°<
Authorisation if outd. T°>
2°C
---°C
2
Conguration
Connection boiler
DHW operating
Complete
Emergency
Minimum shutdown time
Post-circulation
---
20min
HP conguration
HP conguration
HP conguration
HP
Tari󰀨 input conguration
Electrical back-up
Connection boiler
Installation and Operating Manual "1821- EN" - 57 -