10.7 Technical data controller
General
Supply voltage 24 V AC /16 VA 50/60Hz (+40%/-30%)
24 V DC/0.7 A
Type of protection IP54 (front)
IP21 (back)
Ambient and temperature
conditions
IEC60068-2
Operating temperature
range
Storage temperature
range
-10°C…..+60°C (14 °F .....140 °F)
-30°C…..+70°C (-22 °F ......158 °F)
Permissible humidity Relative humidity 90%
No condensation
Noise emission IEC61000-6-3
Noise immunity IEC61000-6-2
Mounting Cabinet door
Digital outputs
Number of outputs 6 (Elektronikon® controller - p.n. 1900 5200 00 …. 1900 5200 09)
9 (Elektronikon® Graphic controller - p.n. 1900 5200 10 …. 1900 5200 19)
Type Relay (voltage free contacts)
Rated voltage AC 250 V AC / 10 A max.
Rated voltage DC 30 V DC / 10 A max.
Digital inputs
Number of inputs 4 (Elektronikon® controller - p.n. 1900 5200 00 …. 1900 5200 09)
10 (Elektronikon® Graphic controller - p.n. 1900 5200 10 …. 1900 5200 19)
Supply by controller 24 V DC
Supply protection Short circuit protected to ground
Input protection Not isolated
Analog inputs
Number of pressure inputs 1 (Elektronikon® controller - p.n. 1900 5200 00 …. 1900 5200 09)
2 (Elektronikon® Graphic controller - p.n. 1900 5200 10 …. 1900 5200 19)
Number of temperature inputs 3 (Elektronikon® controller - p.n. 1900 5200 00 …. 1900 5200 09)
5 (Elektronikon® Graphic controller - p.n. 1900 5200 10 …. 1900 5200 19)