General data of the Modbus RTU interface
32 devices in each segment without repeater, with repeaters expandable to 247Number of devices
Polling between master and slaves (query response)Fieldbus access
01 Read Coil Status
02 Read Input Status
03 Read Holding Registers
04 Read Input Registers
05 Force Single Coil
15 (0FHex) Force Multiple Coils
06 Preset Single Register
16 (10Hex) Preset Multiple Registers
17 (11Hex) Report Slave ID
08 Diagnostics:
00 00 Loopback
00 10 (0AHex) Clear Counters and Diagnostic Register
00 11 (0BHex) Return Bus Message Count
00 12 (0CHex) Return Bus Communication Error Count
00 13 (0DHex) Return Bus Exception Error Count
00 14 (0EHex) Return Slave Message Count
00 15 (0FHex) Return Slave No Response Count
00 16 (10Hex) Return Slave NAK Count
00 17 (11Hex) Return Slave Busy Count
00 18 (12Hex) Return Character Overrun Count
Supported Modbus functions (ser-
vices)
Commands and signals of the Modbus RTU interface
OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command, enable LOCAL,
Interlock OPEN/CLOSE
Process representation output
(command signals)
End positions OPEN, CLOSED
Actual position value
Actual torque value, requires MWG in actuator
Selector switch in position LOCAL/REMOTE
Running indication (directional)
Torque switches OPEN, CLOSED
Limit switches OPEN, CLOSED
Manual operation by handwheel or via local controls
Analogue (2) and digital (4) customer inputs
Process representation input (feed-
back signals)
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
Failure of analogue customer inputs
Process representation input (fault
signals)
The behaviour of the actuator is programmable:
Stop in current position
Travel to end position OPEN or CLOSED
Travel to any intermediate position
Execute last received operation command
Behaviour on loss of communication
Service conditions
Indoor and outdoor use permissibleUse
Any positionMounting position
2 000 m above sea level
> 2,000 m above sea level, on request
Installation altitude
Refer to name plate of actuator controlsAmbient temperature
Up to 100 % relative humidity across the entire permissible temperature rangeHumidity
101
SAEx 07.2 SAEx 16.2/SAREx 07.2 SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive Modbus RTU Technical data

Table of Contents

Other manuals for AUMA SAEx 07.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SAEx 07.2 and is the answer not in the manual?

AUMA SAEx 07.2 Specifications

General IconGeneral
BrandAUMA
ModelSAEx 07.2
CategoryController
LanguageEnglish

Related product manuals