Servicing and maintenance
40
13
Servicing and maintenance
CAUTION
Damage caused by inappropriate maintenance!
à Servicing and maintenance must be carried out exclusively by suitably qualified
personnel having been authorized by the end user or the contractor of the plant.
We recommend contacting our service for any interventions.
à Only perform servicing and maintenance tasks when the device is switched off.
Service & Support
AUMA offers extensive service such as servicing and maintenance as well as cus-
tomer product training. Contact addresses are indicated on our website (http://
www.auma-usa.com).
13.1
Preventive measures for servicing and safe operation
The following actions are required to ensure safe device function during operation:
6 months after commissioning and then once a year
Carry out visual inspection:
Check cable entries, cable glands, blanking plugs, etc. for correct tightness and
sealing. If required, tighten cable glands and blanking plugs with torque in compli-
ance with the manufacturer's specifications.
Check actuator for damage as well as for grease or oil leakage.
When deployed in areas where dust formation represents a potential explosion
hazard, perform visual inspection for deposit of dirt or dust on a regular basis.
Clean devices if required.
Check fastening screws between actuator and gearbox/valve for tightness. If re-
quired fasten screws while applying the tightening torques as indicated in the As-
sembly [}13] chapter.
When rarely operated: Perform test run.
For enclosure protection NEMA 4X/6P
After immersion:
Check actuator.
In case of ingress of water, locate leaks and repair. Dry device correctly and check
for proper function.
13.2
Disconnection from the mains
If the device must be dismantled, for service purposes, it can be isolated from the
mains without having to remove the wiring at the electrical connection.

Table of Contents

Other manuals for AUMA SQEx 12.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SQEx 12.2 and is the answer not in the manual?

AUMA SQEx 12.2 Specifications

General IconGeneral
BrandAUMA
ModelSQEx 12.2
CategoryController
LanguageEnglish

Related product manuals