11 Perm Reset Cleared
This is now a keystuck-reset alarm.
12 EEprom PU Corrupt
On power up, the EEprom test has failed; the water level control
has not been used before, has a faulty EEprom. If the problem
persists after resetting the error, contact Autoflame.
13 Bogus PU State
The EEProm is in a bogus state, if the problem persists after
resetting the error, contact Autoflame.
14 Control Cfg Mismatch
The configuration and commission data do not have matching
control type options. This would occur if the configuration has
been changed after commissioning.
15 Probe 1 Com Data
Probe 1 has corrupt commissioning data. Restart and re-
commission the probes if error persists after resetting error.
16 Probe 2 Com Data
Probe 2 has corrupt commissioning data. Restart and re-
commission the probes if error persists after resetting error.
17 Config Range Check
One or more of the configuration options is outside of the allowed
range.
18 1
st
Low Level
The water level is currently below the commissioned 1
st
Low
position. If the alarm precedes a 2
nd
Low alarm, it will be
automatically replaced by a 2
nd
Low alarm in the log. Once the
water returns to a level above the commissioned 1
st
Low, the error
will remain within the log but it will be automatically reset.
19 High Water Level
The water level is currently above the commissioned High Water
position. This alarm will clear automatically when the water level
is reduced below the commissioned High Water position.
20 Probe 1 Still Water
The signal from probe 1 appears static indicating that the probe is
not in the water.
21 Probe 2 Still Water
The signal from probe 2 appears static indicating that the probe is
not in the water.
22 Probes Diverse
One probe is reading above high water, the other is below 1
st
Low water. Usually caused by auxiliary inputs incorrectly
connected/ optioned. See expansion option 12.1
23 Pre 1
st
Low
The water level is below the commissioned Pre 1
st
Low position.
24 Pre High Water
The water level is above the commissioned Pre High Water
position.
25 Btm Blowdn Software
Fault
Bottom blowdown software fault. Please contact Autoflame.
26 Btm Blowdn Comms
Fault
Bottom blowdown board has a comms failure.
27 Btm Blowdn 24V Fault
Bottom blowdown board – main power failed