EasyManuals Logo

Automated Logic RC642D User Manual

Automated Logic RC642D
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
17
To use an input or output, you must assign it to its corresponding point in the control
program.
1 In WebCTRL's GEO tree, select the equipment controlled by the Room Controller.
2 On the Properties page, select the I/O Points tab.
3 In each point's Num field, type the number of the controller's corresponding input or
output. For example, if you use DO1 on the Room Controller for the point
Fan S/S,
type 1 in the
Num field for Fan S/S.
NOTES
Exp (expander number) is 00 for the Room Controller.
Do not assign the same output number to more than one point.
4 Enter the appropriate values for each input and output in the remaining columns. See
Input values, Output values, Resolution values and Offset/Polarity values below.
NOTE You can also enter these values in EIKON LogicBuilder.
5 If you have not performed the initial download to the Room Controller, you must
download now so you can verify inputs and outputs.
6 To verify each input's operation, force each sensor to a known value, then compare it
to the
Value shown on the Properties page on the I/O Points tab.
7 To verify each output's operation, lock each output to a known condition on the I/O
Points tab, then verify that the equipment operates correctly.
Input
I/O Type
Sensor/Actuator Type
Min/Max
Analog (BAI)
0-5 Vdc
0–5 Volt
Linear Full Range
Engineering values
associated with 0 Vdc
(Min) and 5 Vdc (Max)
1
Thermistor
Thermistor
Select your Thermistor type
or set up and select a
Non-
Linear, Custom Table
2
N/A
Pulse to Analog (BPTA)
3
Pulse Counter
Counter Input
N/A N/A
Digital (Binary) (BBI)
Dry Contact
Dry Contact
N/A N/A
1
The sensor reads a value and sends a corresponding signal (Volt, mA, or psi) to the Room
Controller's physical input. The Analog Input microblock uses the
Min and Max values to linearly
translate the signal into the engineering value used in subsequent control logic. For example, set
Min to 0 and Max to 10 for a 420 mA sensor that measures velocity from 0.0 to 10.0
inches/second so that when the input reads 4 mA, the microblock outputs a value of 0. Similarly,
when the input reads 8 mA, the microblock outputs a value of 2.5.
2
You can set up a custom translation table (page 22) on the driver's Custom Translation Tables
pages in WebCTRL.
3
The control program must have one Pulse to Analog Input microblock for each pulse counting input.
Input values

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automated Logic RC642D and is the answer not in the manual?

Automated Logic RC642D Specifications

General IconGeneral
BrandAutomated Logic
ModelRC642D
CategoryController
LanguageEnglish

Related product manuals