Disabling
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 48
12.7 Disabling Fire Alarm Devices
When you disable a Fire Alarm Device (FAD), the output which
controls the FAD will be disabled. The FAD will thus give no audible
indication.
You can disable a single unit (FAD)/alarm circuit, or all units (FADs) in
a selected Alarm Zone.
A disable time span can be set. When the disable time span expires,
the FAD(s) will automatically be enabled. The single FAD or all FADs
in a selected Alarm Zone can also be enabled manually from the
Enable Menu.
12.8 Disabling Outputs (Loop Outputs/Local Outputs)
When you disable outputs which control Fire Protection Equipment
(FPE), in the event of an alarm / fault, no signals will be sent to trigger
the equipment. (Note that local outputs are not necessary related to
FPE). You can disable a single output, or several outputs.
A disable time span can be set. When the disable time span expires,
the outputs which control Fire Protection Equipment will automatically
be enabled. The outputs can also be enabled manually from the
Enable Menu.
12.9 Disabling Inputs (Loop Inputs/Local Inputs)
When you disable inputs, the signals from external equipment to the
inputs you disable will not be received by the panel/system and no
actions will be taken (for example, activation of general alarm or
external day/night activation). You can disable a single input or
several inputs.
A disable time span can be set. When the disable time span expires,
the signals from external equipment to the inputs will automatically be
enabled, i.e. received by the panel/system.
12.10 Disabling Routing Equipment
When you disable Routing Equipment, including Fire Alarm Routing
Equipment (FARE) and/or Fault Warning Routing Equipment (FWRE),
the output which controls such equipment will be disabled.
Fire Alarm Routing Equipment (FARE): In the event of an alarm, no
fire alarm signals/fault signals will be sent to the fire brigade.
Fault Warning Routing Equipment (FWRE): In the event of a fault, no
fault warning signals will be sent to, for example, the security firm.
A disable time span can be set. When the disable time span expires,
the Routing Equipment which is disabled will automatically be
enabled. The equipment can also be enabled manually from the
Enable Menu.

Table of Contents

Other manuals for Autronica Autroprime

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica Autroprime and is the answer not in the manual?

Autronica Autroprime Specifications

General IconGeneral
BrandAutronica
ModelAutroprime
CategoryFire Alarms
LanguageEnglish

Related product manuals