Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 64
14.14.4 MODBUS Interface Settings
Using the Enter button after selecting MODBUS interface settings
reveals the following properties:
Show Settings
 name
 port (not in use, serial or TCP/IP)
 TCP/IP address
 port number
 mode (slave or master)
 restore factory settings or not (Yes/No)
 slave address (default 128)
 slave ID (default 12)
 Handshake (Yes/No)
 Report Fault (Yes/No)
 Fault Timer (default 10 seconds)
Show Status Registers
 start address
 number of registers
Show Command Registers
 start address
14.14.5 Voyage Data Recorder (VDR)
Using the Enter button after selecting Voyage Data Recorder
settings reveals the following properties:
 name
 port (not in use, serial or TCP/IP)
 port number (default 0)
 restore factory settings or not (Yes/No)
 log volume mini (Yes/No)
 active time (default 4 minutes),
determines how often a message is sent to the VDR to ensure that
there is a proper communication between the system and the VDR.
 update time (default 120 minutes),
determines how often the VDR receives a full update of all fires and
fault statuses.

Table of Contents

Other manuals for Autronica Autroprime

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica Autroprime and is the answer not in the manual?

Autronica Autroprime Specifications

General IconGeneral
BrandAutronica
ModelAutroprime
CategoryFire Alarms
LanguageEnglish

Related product manuals