Introduction
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 6
1.4 Components
The Autroprime Interactive Fire Alarm System comprises the following
components (EN-54) :
Component Abbreviation Description Ref.
Point - Detector or manual call point.
A / D
Control and indicating
equipment
c.i.e. Equipment supplying power to, as well as accepting
fault and alarm signals from detectors. Indicates an
alarm condition audibly and visibly, plus the
location.
B
Power Supply - The source of power for control and indicating
equipment and for items supplied with power from
such equipment.
L
Fire Alarm Devices FAD Equipment giving warning of fire, for example, a
sounder or visual indicator.
C
Fire Alarm Routing
Equipment
FARE Equipment routing an alarm signal from control and
indicating equipment to a Fire Alarm Receiving
Station.
E
Control for Fire Protection
Equipment
FPE An automatic device actuating measures of fire
protection after receiving a signal from control and
indicating equipment (for example, fire
extinguishers, ventilation controllers).
G
Fault Warning Routing
Equipment
FWRE Equipment routing a fault warning signal from
control and indicating equipment to a fault warning
receiving station.
J
Fire Alarm Receiving
Station
- A centre from which the necessary fire protection
measures can be initiated at any time.
F
Fault Warning Receiving
Station
- A centre from which the necessary corrective
measures can be initiated.
K
Automatic Fire Protection
Equipment
- Fire control or fire fighting equipment, for example,
extinguishing installation.
H
B
A
D
L
C
E
F
J
K
Fault Warning
Routing Eq.
Fault Warning
Receiving
Station
G
H
Control
and
indicating
equipment
Automatic Fire
Protection Eq.
Control for
Automatic
Fire Protection Eq.
Fire Alarm
Routing Eq.
Fire Receiving
Station
Fire Alarm
Device
C
Power
Supply
Fire
detectors
Manual
call-points
Points
A
D
Note:
The lines linking the various components on the illustration indicate information flows,
and not physical interconnections.
Item G and H and some other items may need to be provided with a seperate power supply.

Table of Contents

Other manuals for Autronica Autroprime

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica Autroprime and is the answer not in the manual?

Autronica Autroprime Specifications

General IconGeneral
BrandAutronica
ModelAutroprime
CategoryFire Alarms
LanguageEnglish

Related product manuals