Enabling
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 55
13.13 Enabling Delayed Activation
The command Enable Delayed Activation (YES/NO) allows you to
enable or disable all delays that are configured in the system. The
default value is NO.
If Enable Delayed Activation is set to NO, all delays will be disabled
(i.e. immediate actioning).
If Enable Delayed Activation is set to YES, the system will delay the
activation of outputs from points (set to “Override Delay and
Dependency NO”) in detection zones configured as Delayed Action
Detection Zones or Delayed Dependency Detection Zones.
If Day Mode Operation Times are configured or the property for an
onboard input is set to Day/Night Mode, the system will
automatically change the default value NO to YES when the new
configuration is saved and the system is restarted, i.e. all delays
will be automatically enabled.
o If Enable Delayed Activation is set to NO, all delays will be
disabled (i.e. immediate actioning).
o If Enable Delayed Activation is set to YES all delays are again
enabled and controlled by Day Mode Operation Times or
Day/Night inputs.
The example below shows how to enable delayed activation.
To enter the Menu Mode from operation mode or the panel’s idle
state, press and hold down the Enter button
for a few seconds.
Use the arrow down button to scroll down and select Enable.
Press the Enter button
.
Use the arrow down button to scroll down to Delays.
Press the Enter button
twice.
Use the right arrow button to select YES or NO, then press Enter.
To confirm, press Enter once more.