Error search and troubleshooting
48 AVENTICS | ECS Actuator | R417002911–BDL–001–AA
O Check the POWER cable for signs of damage or wear and
replace it if necessary.
O Measure the battery voltage to check if the power supplied
is within the admissible range for the actuator.
Table 12: Admissible power range
O Check if the polarity is correct.
O Check if appropriate, functioning fuses are installed.
Table 13: Fuses
If, after verifying power cables, connectors and battery voltage,
you cannot identify the failure, refer to
www.marex-shipcontrols.com for further information and
support.
MarexECS Actuator 12 VDC 9 - 31,2V
MarexECS Actuator 24VDC 18 - 31,2V
MarexECS Actuator12 VDC 30A
MarexECS Actuator 24VDC 16A