21-2 9424200996
Incomplete Sequence (48) Protection BE1-11m
Figure 21-1. Incomplete Sequence Element Logic Block
Table 21-1. Logic Inputs and Outputs
Name
Function
Purpose
Block
Input
Disables the 48 function when true
Trip
Output
True when the 48 element is in trip condition
Operational Settings
Incomplete sequence operational settings are configured on the Incomplete Sequence (48) settings
screen (Figure 21-2) in BESTCOMSPlus.
Figure 21-2. Incomplete Sequence Settings Screen