BE1-11m Breaker Control Switch (101)
Figure 28-3. Breaker Control Element Logic Block
Table 28-1. Logic Inputs and Outputs
Name
Logic Function
Purpose
Trip
Input
Sets the state of the 101 element to Trip
Close
Input
Sets the state of the 101 element to Close
Informational Tag
Input
Sets an informational tag on the 101 element
Informational Untag
Input
Removes the informational tag from the 101 element
Blocking Tag
Input
Sets a blocking tag on the 101 element
Blocking Untag
Input
Removes the blocking tag from the 101 element
Trip
Output
True if the 101 element is in the Trip state
TSC
Output
True after the Trip output momentarily closes
Close
Output
True if the 101 element is in the Close state
CSC
Output
True after the Close output momentarily closes
Operational Settings
Breaker control element operational settings are configured on the Breaker Control Switch (101) settings
screen (Figure 28-4) in BESTCOMSPlus.
Figure 28-4. Breaker Control Switch Settings Screen