BE1-11m Alarms
Name
Description
Real Time Clock
Real-time clock not set
RTD Comm Receive Fail
BE1-11m cannot communicate with the RTD module. This alarm is set by
the BE1-11m.
RTD Comm Send Fail
RTD module cannot communicate with the BE1-11m. This alarm is set by
the remote RTD module.
RTD Out of Range
RTD out of range. See the RTD Module chapter for acceptable range.
S Demand
Apparent power (VA) demand maximum exceeded
Setting Change
Setting change made by user
Settings Group 0
Setting group 0 is active
Settings Group 1
Setting group 1 is active
Settings Group 2
Setting group 2 is active
Settings Group 3
Setting group 3 is active
SGC Active
Active setting group changed
SGC Logic Override
Setting group control was overridden by logic
Trip Coil Monitor
Monitored trip circuit open
uP Reset Alarm
Microprocessor watchdog circuit timed out
Var Negative Demand
Negative var demand maximum exceeded
Var Positive Demand
Positive var demand maximum exceeded
Watt Forward Demand
Forward watt demand maximum exceeded
Watt Reverse Demand
Reverse watt demand maximum exceeded
Alarm Settings
BESTCOMSPlus Navigation Path: Settings Explorer, Alarm Configuration, Alarms
HMI Navigation Path: Not available through the front panel
Alarms are enabled using BESTCOMSPlus. Use the Settings Explorer to open the Alarm Configuration,
Alarms tree branch. Configure alarms by selecting Disabled, Latching, or Non-Latching from the Minor,
Major, and Logic drop-down menus next to the alarms. Refer to Figure 35-1.
Figure 35-1. Alarm Settings Screen