9424200996 35-3
BE1-11m Alarms
BE1-11m cannot communicate with the RTD module. This alarm is set by
the BE1-11m.
RTD module cannot communicate with the BE1-11m. This alarm is set by
the remote RTD module.
RTD out of range. See the RTD Module chapter for acceptable range.
Apparent power (VA) demand maximum exceeded
Setting change made by user
Setting group 0 is active
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Active setting group changed
Setting group control was overridden by logic
Monitored trip circuit open
Microprocessor watchdog circuit timed out
Negative var demand maximum exceeded
Positive var demand maximum exceeded
Forward watt demand maximum exceeded
Reverse watt demand maximum exceeded
Alarm Settings
BESTCOMSPlus Navigation Path: Settings Explorer, Alarm Configuration, Alarms
HMI Navigation Path: Not available through the front panel
Alarms are enabled using BESTCOMSPlus. Use the Settings Explorer to open the Alarm Configuration,
Alarms tree branch. Configure alarms by selecting Disabled, Latching, or Non-Latching from the Minor,
Major, and Logic drop-down menus next to the alarms. Refer to Figure 35-1.
Figure 35-1. Alarm Settings Screen