9424200996 48-9
BE1-11m BESTlogicPlus
Name
Description
Symbol
Motor Status logic block is true. The emergency
start condition remains until the thermal capacity
drops below 100%, the motor stops, or the motor
does not start for one minute after the emergency
start was requested.
Motor is Started This input can be used with
current or stand alone to detect the motor has
started as determined by the Motor Start
Detection setting.
Motor is Stopped This input can be used with
current or stand alone to detect the motor has
stopped as determined by the Motor Start
Detection setting.
Logic Outputs
Running This output is true when the motor is
running. The Motor Start Detection setting
controls how the BE1-11m identifies when a
motor is running.
Current Only
From a normal motor start - The motor is
deemed runningwhen all three phases of
current drop below 2 X FLA for 100 ms.
From a soft motor start - The motor is deemed
runningwhen all three phases of current are
below 2 X FLA, but above 5% FLA for 300 ms.
Current and Contacts
From a normal motor start - The motor is
deemed runningwhen all three phases of
current drop below 2 X FLA for 100 ms and
the Motor is Started logic input of the Motor
Status logic block becomes true.
From a soft motor start - The motor is deemed
runningwhen all three phases of current are
below 2 X FLA, but above 5% FLA for 300 ms,
and the Motor Started logic input of the Motor
Status logic block becomes true.
Contacts Only
The motor is deemed runningwhen, from a
stopped condition, the Motor is Started logic input
of the Motor Status logic block becomes true.
Starting This output is true when the motor is
starting. The Motor Start Detection setting
controls how the BE1-11m identifies when a
motor is started.
Current Only
Normal start - The motor is deemed “starting”
when, from a stopped condition, the current
on any phase increases to greater than 2 X
FLA.
Soft start - The motor is deemed “starting”
when, from a stopped condition, the current
on any phase is below 2 X FLA, but above 5%
FLA for 300 ms.
Current and Contacts
Normal start - The motor is deemed “starting”
when, from a stopped condition, the current
on any phase increases to greater than 2 X
FLA and the Motor is Started logic input of the
Motor Status logic block becomes true.
Soft start - The motor is deemed “starting”
when, from a stopped condition, the current