Communication BE1-11m
Note
Physical Port Selection (Ethernet or RS-485) is available only for
Ethernet Protocol options 3 and 4 and only when RS-485 port protocol
option is N (None). RTD module communication over RS-485 is not
available when the physical port for DNP communication is RS-485.
Figure 49-7. DNP Settings, Miscellaneous Settings Screen
Unsolicited Response Support
The Unsolicited Response Support screen (Figure 49-8) configures BE1-11m unsolicited responses over
a DNP network and selects the classes of events that trigger the responses.
Figure 49-8. DNP Settings, Unsolicited Response Support Screen
Default Variations
The Default Variations screen (Figure 49-9) is used to configure the binary and analog inputs and analog
output status.