9424200996 52-3
BE1-11m Device Information
Figure 52-3. Basler Electric Device Package Uploader
Use the Open button to browse for the device file that you obtained from Basler Electric. Place a
checkmark next to the file you want to upload. Click the Upload button. The BE1-11m will reboot
automatically after the firmware upload is complete.
After rebooting, the Relay Trouble LED on the front panel is lit and Defaults Loaded is displayed on the
Relay Alarms screen. To reset the alarm, use the Metering Explorer in BESTCOMSPlus to navigate to the
Status, Alarms screen (Figure 52-4) and click the Reset Relay Alarms button. This alarm can also be
reset through the front panel by navigating to Metering > Status > Alarms > Relay Alarms and pressing
the Reset button. Admin access is required to reset the Defaults Loaded alarm. The default username is
“A” and the default password is “A”. Alarm reset can also be set outside of security control, allowing reset
without logging in. Refer to the Security chapter for more information. Restore your settings file.
Figure 52-4. BESTCOMSPlus Alarms Screen