BE1-11m Configuration
Tap
This setting adjusts the measured currents to eliminate magnitude mismatch prior to being used by the
optional 87 differential function.
Phase VT Setup
The BE1-11m requires setting information about the VT ratio, the phase connections, and the operating
modes for the 27/59 and 27R functions. These settings are used by the metering and fault reporting
functions to display measured quantities in primary units. The voltage input circuit settings also determine
which power measurement calculations are used. Most of these connections such as 3W-D, 4W-Y, AN, or
AB are self-explanatory.
Auxiliary VT Setup
The auxiliary voltage input (Vx) connection can be set for AB, BC, CA, AN, BN, CN, or Ground. The Vx
input connection is set to Ground when connected to a source of ground unbalance voltage or residual
voltage such as a generator grounding resistor, broken delta VT connection, or capacitor bank star point.
Bus CT Selection
The CT Source setting selects the Bus CT to use in calculations for metering, fuse loss (60FL), and power
protection (32, 40Q, 55) on protection systems equipped with two sets of CTs.
Settings
Sensing transformers settings are configured on the Sensing Transformers settings screen (Figure 53-2)
in BESTCOMSPlus.
Figure 53-2. Sensing Transformers Settings Screen
Display Units
The Display Units screen is shown in Figure 53-3.
System Units
This setting configures the BE1-11m to display and report temperature in English or metric units of