EasyManuals Logo

Basler BE1-11m User Manual

Basler BE1-11m
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #320 background imageLoading...
Page #320 background image
55-2 9424200996
Acceptance Testing BE1-11m
IRIG Verification (if used)
Purpose: To verify that the BE1-11m acquires and updates IRIG time and date information.
Step 1: Connect a suitable IRIG source to BE1-11m terminals A1 (+) and A2 ().
Step 2: Upon receiving the IRIG signal, the BE1-11m clock will be updated with the current time, day,
and month. Verify this on the Metering > Status > Real Time Clock screen on the front-panel
display.
Contact Sensing Inputs
Purpose: To verify that the BE1-11m senses hardware input status.
Step 1: Apply an external voltage source within the range of the voltages listed in Table 55-2 to contact
sensing inputs IN1 (B1/B2), IN2 (B3/B4), IN3 (B5/B6), IN4 (B7/B8), IN5 (E1/E2), IN6 (E3/E4),
and IN7 (E5/E6).
Table 55-2. Contact Sensing Turn-On Voltages
Style Option Nominal Input Voltage
Contact Sensing Turn-On Voltage*
Jumper Installed
(Low Position)
Jumper Not Installed
(High Position)
Mxx1xxxxxxxxxx 48 Vdc or 125 Vac/dc 26 to 38 Vdc
69 to 100 Vdc
56 to 97 Vac
Mxx2xxxxxxxxxx 125/250 Vac/dc
69 to 100 Vdc
56 to 97 Vac
138 to 200 Vdc
112 to 194 Vac
Mxx3xxxxxxxxxx
24 Vdc
n/a
Approx. 5 Vdc
* For information on setting contact-sensing input jumpers, refer to the Contact Inputs and Outputs
chapter.
Step 2: To verify that all inputs have been detected, use the Metering Explorer in BESTCOMSPlus to
open the Status, Inputs screen.
Control Outputs
Purpose: To verify that the BE1-11m senses hardware output status.
Step 1: Connect to the BE1-11m through BESTCOMSPlus.
Step 2: Use the Metering Explorer to open the Control, Output Override screen.
Step 3: Click on the Disabled button for Output #1. The button changes to Enabled indicating that the
output control override capability of the relay is enabled.
Step 4: Select Set from the Action drop-down menu and click on the green arrow button to energize
Output #1. Verify that the Output #1 Status LED, located on the Output Override screen of
BESTCOMSPlus, turns on. Navigate to the Metering > Status > Outputs screen on the front-
panel display and verify that Output #1 changes state.
Step 5: Select Reset from the Action drop-down menu and click on the green arrow button to de-
energize Output #1. Verify that the Output #1 Status LED, located on the Output Override
screen of BESTCOMSPlus, turns off. Navigate to Metering > Status > Outputs on the front-
panel display and verify that Output #1 changes state.
Step 6: Verify that the sequence of events recorder logged the events by using the Metering Explorer in
BESTCOMSPlus to open the Reports, Sequence of Events screen.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Basler BE1-11m and is the answer not in the manual?

Basler BE1-11m Specifications

General IconGeneral
BrandBasler
ModelBE1-11m
CategoryProtection Device
LanguageEnglish

Related product manuals