BE1-11m Logic Timers (62) Test
switch in the SER report uses the programmable name parameters applied to the switch. Figure
75-3 illustrates the timing relationship of the 43-1 switch and 62-1 timer.
Figure 75-3. Pickup/Dropout Mode
Step 10: (Optional.) Repeat steps 1 through 9 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, and 62-8.
Step 11: (Optional.) Repeat steps 1 through 10 for settings group 1, 2, and 3.
One-Shot/Non-Retriggerable Mode
Step 1: Use BESTCOMSPlus to send the operational settings in Table 75-2 to the BE1-11m. Retain the
logic settings from Figure 75-1.
Table 75-2. Operational Settings (One-Shot/Non-Retriggerable Mode)
Setting
Value
BESTCOMSPlus Screen
Description
62-1 Mode
One-Shot/Non-
Retriggerable
Control, Logic Timers (62)
Sets 62-1 to One-Shot/Non-
Retriggerable mode
62-1 Time
Delay 1 (T1)
400 ms
Control, Logic Timers (62)
Sets 62-1 pickup time delay to
400 ms
62-1 Time
Delay 2 (T2)
20,000 ms
Control, Logic Timers (62)
Sets 62-1 dropout time delay
to 20,000 ms
43-1 Mode
Pulse
Control, Virtual Control
Switches (43)
Sets 43-1 to Pulse mode
62-1 Target
Enabled
Target Configuration,
Targets screen.
Enables 62-1 target
Step 2: Step 4 supplies the 62-1 timer with a momentary initiate input by pulsing the 43-1 switch from
an OFF state to an ON state and then back to an OFF state. You can view the state changes of
the 43-1 switch at the Metering > Control > Virtual Switches screen on the front-panel display.
Step 3: Close communication with BESTCOMSPlus.
Note
The 43-1 switch action is performed twice in this test. To illustrate the
action of the timer mode, step 4 should be executed as quickly as
possible. Ideally, this test should be repeated within 20 seconds. If this
is a problem, try extending the dropout timer setting (Time Delay 2).
Step 4: Using the front-panel display, navigate to Metering > Control > Virtual Switches. Highlight the
first switch (43-1) and press the Right key on the front panel to enter the 43-1 control screen.
Use the Edit key to login. Highlight Operate and then press the Edit key to change the state of
the 43-1. Using the Up/Down keys select PUL and then press the Edit key.
Step 5: Use the Metering Explorer in BESTCOMSPlus to open the Reports, Sequence of Events
screen. Verify that an OFF-ON-OFF pulse action was logged and that approximately 400 ms
P0
035
-30
0
2-2
7-0
6
62-x
Block
Initiate