77-2 9424200996
Breaker Control Switch (101) Test BE1-11m
Figure 77-1. BESTlogicPlus Settings
Step 5: Place the 101 in the CLOSE position by using the Metering Explorer in BESTCOMSPlus to
open the Control, Breaker Control Switch tree branch. Click on the CLOSE button to select it.
Login may be required. The green selection LED will begin to flash. Within 25 seconds, click on
the CLOSE button a second time to operate it. The green selection LED will stop flashing and
the close status LED will light.
Result: OUT3 closes for 200 ms and returns to the open state. OUT4 closes (CLOSE state) and remains
closed.
Figure 77-2 illustrates the breaker control switch state diagram.
Figure 77-2. Breaker Control Switch State Diagram
Functional Test Report
Pass/Fail
P / F
Trip
TSC
Close
CSC
P0035-39
02-24-06

Table of Contents