84-4 9424200996
Settings Calculation Examples BE1-11m
General Settings
Display Units
Settings in this example are in metric and secondary units, based upon multiples of FLA (Full Load Amps)
and phase-to-phase voltages, unless otherwise specified. Phase-to-phase voltages are configured during
phase VT setup.
Use the Settings Explorer in BESTCOMSPlus® to navigate to the General Settings, Display Units screen.
Select Metric for System Units and Secondary Units for Settings Display Modes, Thresholds. Refer to
Figure 84-3.
Figure 84-3. General Settings, Display Units Screen
Style Number
The BE1-11m style number shown in Figure 84-4 is used in this application example. The style number is
defined below.
Figure 84-4. BE1-11 Style Number
M ......... Application Option ...................... Motor
6 .......... Phase CT Option ........................ CT1 - 5 Amp Nominal / CT2 - 5 Amp Nominal
D .......... Ground CT Option ...................... CT1 - 5 Amp Nominal / CT2 - 5 Amp Nominal
1 .......... Power Supply Option ................. 48/125 Vac/dc
M ......... RS-485 Port Protocol ................. Modbus
1 .......... Ethernet Protocol ....................... BESTnetPlus Only
J .......... Case Option ............................... Vertical Case
2 .......... Alarm Contact Option ................. Normally Closed (closes upon power removal / watchdog failure)
P .......... Option 1 ...................................... Phase Differential
0 .......... Network Connections ................. Copper
E .......... Language ................................... English
0 .......... Option 2 ...................................... None
00 ........ Firmware Option ......................... Latest Release