EasyManua.ls Logo

Basler BE1-11m - Page 557

Basler BE1-11m
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9424200996 84-13
BE1-11m Settings Calculation Examples
Select three-phase mode and set the Pickup setting to 71.77 Secondary A as shown in Figure 84-15.
Figure 84-15. Protection, Current, Instantaneous Overcurrent (50-1) Screen
Instantaneous Overcurrent (50-2) - Ground Fault Protection
The system is solidly grounded so that a ground fault draws current in the magnitude of a three-phase
fault per IEEE C37.96-2000, IEEE Guide for AC Motor Protection. To determine the three-phase fault
current, consider that the motor subtransient reactance of 0.15 is the limiting impedance. The pickup
setting is calculated using Equation 84-7. A pickup setting of 1/3 of the instantaneous three-phase fault
current is recommended per IEEE C37.96-2000, IEEE Guide for AC Motor Protection.
=
1
"

 
1
3
=
1
0.15
363
80
1
3
= 10.08 
Equation 84-7. 50-2 Pickup
Select 3I0 (residual) mode and set the Pickup setting to 10.08 Secondary A as shown in Figure 84-16.
Figure 84-16. Protection, Current, Instantaneous Overcurrent (50-2) Screen
Instantaneous Overcurrent (50-3) - Unbalance Protection
The NEMA MG-1 standard states that the existence of unbalanced voltage feed results in four to 10 times
the current imbalance. The negative-sequence voltage unbalances should not exceed 5 percent. This
application uses negative-sequence current as the input to an overcurrent element to sense unbalance
conditions. For conservative protection, choose 4 5%, which is 20 percent imbalance. A 10 second
delay is appropriate because the heating is slow (motor mass is large). The pickup setting calculation is
shown in Equation 84-8.

Table of Contents

Related product manuals