Settings Calculation Examples BE1-11m
Motor Manufacturer Data
Motor manufacturer data should be reviewed before configuring the BE1-11m. Typical motor
manufacturer data is listed below.
GENERAL
HP .....................................................................5000 HP
System Frequency ............................................60 Hz
Motor Rotation ..................................................1200 RPM
Bus Voltage ......................................................12 kV
Full-Load Amps (FLA, Synchronous) ...............205 A
Full-Voltage No-Load Stator Current in Sync ...128 A (no excitation)
Full-Voltage Line Current (95% Speed) ...........392 A (no excitation)
Maximum Locked Rotor Current (Max. LRA) ...755 A
Service Factor...................................................1.15
Power Factor Minimum .....................................0.90
Stator Insulation Class ......................................F (155°C per NEMA MG-1 Standard)
Ambient Temperature Rating ...........................40°C
Stator Temperature Rise ..................................76°C
Subtransient Reactance Xd.............................0.368 pu, 4263 kVA base
Hot Safe Stall Time ...........................................8.5 seconds
Cold Safe Stall Time .........................................10.7 seconds
FIELD
Excitation (Brushless) .......................................22 kW @ 51 Vdc
No Load Saturation
P.U. Line Volts 0.25 0.50 0.75 1.00 1.10 1.20 1.30
Field Amps 34.3 68.9 105.9 144.4 161.8 181.8 213.5 (motor)
0.3 0.7 1.1 1.3 1.5 1.6 1.9
(exciter)
Rated P.F. Excitation
P.U. Load 0.25 0.50 0.75 1.00 1.15
Field Amps 189.1 248.3 314.3 384.9 429.4 (motor)
1.7 2.2 2.9 3.5 4.6
(exciter)
RTDs
Six Stator RTDs ................................................100 , 3-wire element, platinum
Two Bearing RTDs ...........................................100 , 3-wire element, platinum
One Ambient RTD ............................................100 , 3-wire element, platinum
STARTING
Minimum Starting Voltage ................................85%
Starting Performance
Starting Torque ....................................52%
Pull-In Torque ......................................115%
Pull-Out Torque ...................................151%
Inrush ...................................................368%
Pull-In Slip............................................5%
Accelerating Time ................................2.4 seconds
Motor WK
2
...........................................8391
Load WK
2
.............................................752