BE1-11m Settings Calculation Examples
Table 206 lists the allowable time on the squirrel cage winding at 100% voltage.
Table 206. Allowable time on Squirrel Cage Winding at 100 Percent Voltage
% Speed
0
50
75
95
Seconds
16.7
25
34
288
Acceleration Time to Synchronous Speed (100% V) .............. 2.42 seconds
Acceleration Time to Synchronous Speed (85%) V) ............... 4.27 seconds
Power Factor relay (55) for pullout 0.90 P.F. lag; locked out until after 2.5 seconds
CONSECUTIVE STARTS
Ambient Temperature .................................... 2 starts
Idle Starts Time ................................ 60 minutes
Running Starts Time ......................... 30 minutes
Operating Temperature ................................. 1 start
Idle Starts Time ................................ 90 minutes
Running Starts Time ......................... 60 minutes
THERMAL TIME CONSTANT
Ambient (Stopped Condition) ........................ 190 minutes
Operating (Running Condition) ...................... 60 minutes
RUNNING
Ride-Through Minimum Voltage .................... 75% for 30 seconds
Bearing Alarm Temperature .......................... 90°C
Bearing Trip Temperature ............................. 95°C
OPERATING PERFORMANCE
Load % ........................................................... 100 ...... 75 ........ 50
Efficiency % ................................................... 97.23 ... 97.22 ... 96.85
OTHER
Name
Location
The required motor curves are shown in Figure 84-31. Curve A shows the thermal limits at 100 percent of
the starting voltage. Curve B shows the thermal limits at 85 percent of the starting voltage. Figure 84-32
shows the synchronous motor V curves indicating operational parameters of load an power factor.