EasyManua.ls Logo

Basler BE1-11m - Page 581

Basler BE1-11m
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9424200996 84-37
BE1-11m Settings Calculation Examples
= 1.7  
(
125%  + 2%  
)
   
1

= 1.7
(
1.25 + 0.02
)
755
1
60
= 27.17 
Equation 84-26. 50-1 Pickup
Set for three-phase mode so that any phase exceeding the setting will pick up the element. Set the
Pickup setting to 27.17 Secondary A. Typically, CT circuit 1 is used because it is on the feed side of the
motor. See Figure 84-46.
Figure 84-46. Protection, Current, Instantaneous Overcurrent (50-1) Screen
Instantaneous Overcurrent (50-2) - Ground Fault Protection
The system is solidly grounded so that a ground fault draws current in the magnitude of a three-phase
fault per IEEE C37.96-2000, IEEE Guide for AC Motor Protection. To determine the three-phase fault
current, consider that the motor subtransient reactance of 0.368 is the limiting impedance. The pickup
setting is calculated using Equation 84-27. A pickup setting of 1/3 of the instantaneous three-phase fault
current is recommended per IEEE C37.96-2000, IEEE Guide for AC Motor Protection. During starting, CT
saturation can produce false residual currents, so we use the running mode current FLA. The circuit CT
ratio (CTR) is 60.
=
1
"

 
1
3
=
1
0.368
205
60
1
3
= 3.09 
Equation 84-27. 50-2 Pickup
Select 3I0 (residual) mode and set the Pickup setting to 3.09 Secondary A as shown in Figure 84-47.

Table of Contents

Related product manuals