EasyManua.ls Logo

Basler BE1-11m - Page 587

Basler BE1-11m
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9424200996 84-43
BE1-11m Settings Calculation Examples
2   = 
1

2 = 205
1
60
2 = 6.83
2   =
6.83
2.0
= 3.42
Equation 84-36. 2
nd
Slope (Starting) Pickup Setting
Figure 84-55 shows an example of 2
nd
Slope Restrained Operation.
Figure 84-55. 2
nd
Slope Restrained Operation Example
Based upon good engineering practices during starting mode to overcome dc offset and CT mismatches,
set Restraint Slope 2 % at 1.7 times the running mode slope and add a 25 percent margin. Restraint
Slope 2 % is calculated using Equation 84-37.
  2 % =  25%   1 % = 1.7 1.25 0.15% = 32%
Equation 84-37. Restraint Slope 2 %
Set the 2
nd
Slope Pickup (starting) at 3.42 and the Restraint Slope 2% at 32.
Alarm
The BE1-11m provides a Slope % alarm for cases where high loads or through faults cause unbalance in
the differential. The Slope % Alarm is calculated in Equation 84-38.
 % = 1.5   2 % = 1.5 32% = 48%
Equation 84-38. Slope % Alarm
The setting range for Slope % Alarm is 50 to 100 in increments of 1, so a Slope % Alarm of 50% is used
for this example.
The Current Differential (87) screen is shown in Figure 84-56.

Table of Contents

Related product manuals