BE1-11m Frequency (81) Protection
Sensing Source
Frequency ROC protection can be applied to the voltage sensed at the BE1-11m phase VT input or
auxiliary VT (Vx) input. A Source setting of Phase VT selects the voltage sensed at the phase VT input
and a Source setting of Aux VT selects the voltage sensed at the Vx input.
The Auxiliary VT (Vx) input can be connected to a voltage transformer on the motor side of the breaker to
determine if the motor is spinning when the breaker is open.
Pickup and Trip
When the rate of frequency change (expressed in hertz per second) exceeds the threshold established by
the Pickup setting for three consecutive sensing voltage cycles, the element Pickup output becomes true.
Pickup detection time varies according to the value of the fault frequency. When the frequency greatly
exceeds the pickup setting, pickup detection occurs very quickly. More precise and less quick pickup
detection occurs when the fault frequency is much closer to the Pickup setting. Pickup detection times are
summarized as follows:
Faults exceeding the pickup setting by 0.57 Hz/s are detected in 2 cycles
Faults exceeding the pickup setting by 0.24 Hz/s are detected in 4 cycles
Faults exceeding the pickup setting by 0.08 Hz/s are detected in 8 cycles
No pickup detection time will be greater than 16 cycles
In BESTlogicPlus, the Pickup output can be connected to other logic elements to annunciate the condition
or control other elements in logic.
Assertion of the Pickup output initiates a timer, which begins timing toward a trip. The duration of the timer
is established by the Time Delay setting. A Time Delay setting of zero (0) makes the 81 element
instantaneous (with the exception of the pickup detection time).
If an ROC pickup condition persists for the duration of the element Time Delay setting, the element Trip
output becomes true. In BESTlogicPlus, the Trip output can be connected to other logic elements or a
physical relay output to annunciate the condition and initiate corrective action. If a target is enabled for the
element, the BE1-11m will record a target when the Trip output becomes true. See the Fault Reporting
chapter for more information about target reporting.
If the pickup condition subsides before the element time delay expires, the timer and Pickup output are
reset, no corrective action is taken, and the element is rearmed for any other occurrences of a frequency
ROC fault.
Inhibit Functions
Frequency ROC protection can be inhibited by the degree of underfrequency or overfrequency or the
percentage of negative sequence voltage.
The Overfrequency Inhibit setting disables frequency ROC protection when the sensed frequency
exceeds the setting threshold. Likewise, the Underfrequency Inhibit setting disables frequency ROC
protection when the sensed frequency decreases below the setting threshold.
Frequency ROC protection can be inhibited when the percentage of negative sequence voltage exceeds
the limit established by the Negative Sequence Inhibit setting. A Negative Sequence Inhibit setting of zero
(0) inhibits this feature.
Element Blocking
This input allows for logic supervision or control of the element.
Each frequency protection element has a Block logic input, which when true, disables an element by
forcing the Trip and Pickup outputs to logic 0 and resetting the element timer. An element Block input is
connected to the desired logic in BESTlogicPlus.