EasyManua.ls Logo

Basler BE1-11m - Page 96

Basler BE1-11m
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15-4 9424200996
Phase Current Differential (87) Protection BE1-11m
Flux-Balancing Configuration
In a flux-balancing arrangement, the phase and neutral side of each phase of the winding route through a
CT so the net flux is zero under normal conditions. See Figure 15-4. Typically, a three-phase
Instantaneous Overcurrent (50) element provides flux-balancing protection.
Figure 15-4. Flux-Balancing Connections
If a BE1-11m is equipped with the differential option, an alternate method can be used to configure flux-
balancing protection. In the Phase Differential (87) window of BESTCOMSPlus, set the mode to Flux
Balance. In this mode, the BE1-11m compares the setting in the Flux Balance Pickup setting (secondary
A) on a per-phase basis to the current in CT circuit 1 (CT1). The link between CT1 and the Flux Balance
mode is fixed in firmware; the flux balance circuit must be wired to CT circuit 1 (terminals D1 through D8
in Figure 15-4). The “Flux Balance” mode is equivalent to a three-phase 50 element.

Table of Contents

Related product manuals