Error detection and troubleshooting
Compact manual b maXX
®
BM4400, BM4600, BM4700
Document no.: 5.06014.02
67
of 94
8
Error power Supply P0205
Error power unit P0206
59 Timeout when waiting for the RST sig-
nal of the slaves
IS Execute a restart
60 CRC error in
SPI transmission module f controller
adjustable Error indicates that there are high EMC interfer-
ences; please reduce these.
Contact Baumüller.
61 CRC error in
SPI transmission
Controller f module
adjustable Error indicates high EMC interferences; please
reduce these.
Contact Baumüller.
62 to 63 reserved
not assigned = 0
Error no. Meaning Reaction Troubleshooting
Error no. Meaning Reaction Troubleshooting
64 Mains failure adjustable Restore the connection to the power supply
65 Phase failure IS Check if all phases are correctly connected and
voltage-carrying
66 Mains undervoltage IS Assure the compliance with the mains specifi-
cations (see techn. data)
67 Mains overvoltage IS Assure the compliance with the mains specifi-
cations (see techn. data)
68 Undervoltage 24V IS Assure the compliance with the mains specifi-
cations (see techn. data)
68 to 79 reserved
not assigned = 0
79 Mains monitor collected errors Adjustable See P0236
Error no. Meaning Reaction Troubleshooting
80 Communication error after HIPER-
FACE
®
specification
IS see ZError power unit - serial interface
P0233– on page 77
(= 3. level)
81 Heatsink temperature IS Let the device cool down and/or reduce the
load
82 U DC link overvoltage IS Reduce the DC link voltage
83 Overcurrent IS Reduce the load and check the current control-
ler settings as well as the cabling and the motor