Operation
45
TGH1394en/05.2007
Residual current
The residual current flowing through the measuring current transformer
is continually measured and displayed.
If the residual current exceeds 100 mA (EDS460/490) or 10 mA
(EDS461/491), this information is displayed.
If the residual current exceeds 10 A (EDS460/490) 1 A (EDS461/491), this
information is displayed. Once the residual current reaches values of
this magnitude, reliable insulation fault location becomes impossible.
ALARM 1/1
Residual current
> 10 A
Addr.: 2 Channel: 1