Tests and service
65
TGH1394en/05.2007
7.4.2 Device error display (channel-related)
LED "Alarm 1" lights up. The common alarm relay switches. The EDS...-
D displays:
Line 1: FAULT,
Alarm 1 of 1 pending alarm
Line 2: Alarm status and alarm text
No alarm
Alarm
Line 3: Error code (refer to "Display device error" on page 64)
Line 4: BMS bus address of the EDS and the measuring channel
on which the alarm has occurred.
Possible causes:
Incorrect basic programming of the EDS.
Wrong p.c.b. assembly at four consecutive channels.
Internal memory fault.
Faulty channels after test.
Fault 1/1
Device error
11
Addr.: 2 Channel: 4