Operation
46
TGH1394en/05.2007
6.6.2 Menu 2: History
The non-volatile history memory saves up to 300 data records (alarms,
device errors). If the history memory is full, the oldest entry will be de-
leted in the event of an alarm to create space for the new entry. For de-
tails about erasing the entire history memory refer to "chapter 6.6.3.4
Settings menu 4: History".
Line 1: Event number (if applicable): TEST.
Line 2: Event start: Date / time
Line 3: Event acknowledgement (e.g. alarm deleted at IRDH575,
PRC1470, MK2430, FTC470...):
Datum / Uhrzeit
Line 4: Event end: Date / time
1. If you are searching for an event that occurred at a specific time, use
the arrow keys to scroll to the required entry.
2.
Use the "
" key to call up details about the current history memory entry.
Line 1: Data record number.
Line 2: Alarm/device error designation.
Line 3: Minimum and maximum measured value.
Line 4: Address and measuring channel of device sending the
message
History no. 297
Start:
21.11.2005 / 15:57:00
Quit:
End:
21.11.2005 / 16:07:03
History no. 297
Insulation fault
Min. 2mA/Max.50mA
Addr.:2 Channel:1