EasyManua.ls Logo

Bender EDS460 - Technical Data EDS460;490; EDS461;491

Bender EDS460
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data
68
TGH1394en/05.2007
8.3 Technical data EDS460/490 / EDS461/491
Insulation coordination acc. to IEC 60664-1 / IEC 60664-3
Rated insulation voltage....................................................................................................................................AC 250 V
Rated impulse voltage/pollution degree............................................................................................................ 4 kV / III
Protective separation (reinforced insulation) between:
............................................................................(A1, A2) - (K1, L…K12, R / RT / T, AB) - (11, 12, 14) - (21, 22, 24)
Voltage test acc. to IEC 61010-1 .........................................................................................................................2.21 kV
Supply voltage
Supply voltage U
S
....................................................................................................................see ordering information
Frequency range U
S
...............................................................................................................................AC 42…460 Hz
Power consumption............................................................................................................... 10 VA ( EDS460 / 461)
................................................................................................................................................. 14 VA (EDS490 / 491)
Measuring circuit
Nominal system voltage U
n
................................................................refer to IRDH575, PGH47x... (EDS460, EDS490)
...................................................................................................... AC 20…276 V, DC 20…308 V (EDS461, EDS491)
External measuring current transformer type .............................................W…, WR…, WS… (EDS460, EDS490)
................................................................................................................W…/8000, WS…/8000 (EDS461, EDS491)
CT monitoring ..............................................................................................................................................on/off (on)*
Load ........................................................................................................................................................................10 Ω
Rated insulation voltage (measuring current transformer) ..................................................................................800 V
Response sensitivity......................................................................................................2…10 mA (EDS460 / EDS490)
......................................................................................................................................0.2…1 mA (EDS461 / EDS491)
Rated frequency.....................................................................................................................................50 / 60 / 400 Hz
EDS function measuring range.....................................................................................2…50 mA (EDS460 / EDS490)
......................................................................................................................................0.2…5 mA (EDS461 / EDS491)
RCM function measuring range............................................................................ 100 mA…10 A (EDS460 / EDS490)
................................................................................................................................... 10 mA…1 A (EDS461 / EDS491)
Number of measuring channels (per device/system) ....................................................................................12 / 1080
Specified time
Response delay t
on
............................................................................................................................................. 0…24 s
Release delay t
off
................................................................................................................................................ 0…24 s
Scanning time for all channels .............................................................................................................approx. 4…10 s

Table of Contents

Other manuals for Bender EDS460