Tests and service
64
TGH1394en/05.2007
7.4 Troubleshooting
7.4.1 Display device error
An "error code" is displayed if a fault occurs. Please have this device infor-
mation to hand if you should need to contact us for assistance by telephone.
Display in the event of a fault
xx = Error code
Error
code
Description
1 Measurement technique: Fault parameter memory (EEP-
ROM/FLASH)
2 Measurement technique: Fault data memory (RAM)
4 Measurement technique: No boot loader available.
11 Measurement technique: Device not calibrated.
12 Measurement technique: Wrong measurement p.c.b., incor-
rect mounting
13 Measurement technique: Hardware error after performing a
self test
71 BMS interface: No master available resp. has not been que-
ried by a master for five minutes
72 BMS interface: Fault RS-485 interface
EDS...-D
EDS...-L
Device error: xx Er
xx (alternately displayed)