Operation
54
TGH1394en/05.2007
3.Device error
on Relay switches in the event of a device error.
off Relay does not switch in the event of a device error.
4.Ext. alarm
on Relay switches in the event of an external alarm.*
off Relay does not switch in the event of an external alarm.*
* Alarm on an external device the address of which has been set to "on" in the
"Alarm addresses" menu. (see "Settings menu 7: Alarm addresses" on page 54).
6.6.3.4 Settings menu 4: History
Here the entire history memory can be deleted. Use the "" key to con-
firm that the memory is to be deleted.
6.6.3.5 Settings menu 5: Language
Select the language for menu and alarm texts.
Setting options: English, German or Français.
6.6.3.6 Settings menu 6: Interface
Set the BMS bus address of the EDS... .
Setting range: EDS...-D Address 1…90
EDS...-L Address 1…90
6.6.3.7 Settings menu 7: Alarm addresses
Setting of the bus addresses (1...150) externally connected to the BMS
bus, the alarm messages of which are to be displayed on this EDS...-D.
Set the addresses of devices whose messages are to be displayed to "on".
Addresses set to "on"are monitored for presence on the BMS bus; if a
device cannot be found on the bus, a corresponding message will ap-