Commissioning
33
EDS460-490_D00085_01_M_XXEN/02.2016
Deactivation of the CT monitoring recommended
The connection and short-circuit monitoring of the measuring current trans-
former is deactivated ex works. It serves primarily used to facilitate the com-
missioning of the EDS system (it can be activated for this task). In the standard
measurement mode, the monitoring function may cause false alarms due to
interference signals occurring in the environment. Therefore, we recommend
to deactivate the CT monitoring function after successful commissioning, see
page 54.