Operation
40
EDS460-490_D00085_01_M_XXEN/02.2016
EDS…-L: All alarm LEDs light up.
Once the test has been completed, all LEDs must go out again, with the excep-
tion of the "ON" LED.
6.3.4 Resetting saved alarm messages (RESET)
If the fault memory is enabled, the alarm status will remain, even after the
cause of the fault has been eliminated, until a "RESET" is carried out.
Press the "ESC" button to exit the display of the current alarm message. To car-
ry out a RESET:
Select the standard display, then press and hold down the "RESET" but-
ton on the EDS… front panel for at least one second
Press the external reset button connected to the EDS…
Send a reset command via the BMS bus
EDS…-D only: Call the "RESET" function in the Control menu
Stored alarm messages that are no longer pending are reset, the alarm relay
drops out, the ALARM LEDs go out and there are no longer any alarm messa-
ges on the BMS bus. The EDS…-D shows the progress of the reset operation.