Operation
51
EDS460-490_D00085_01_M_XXEN/02.2016
3.Frequency
Select the rated frequency of the monitored system. This must be set correct-
ly, otherwise the EDS… will not be able to evaluate the locating current pulse
accurately.
Configurable values: DC, 50 Hz, 60 Hz, 400 Hz
4.System type
Select the type of distribution system for the system being monitored.
Configurable values: DC, AC, 3 AC.
6.6.3.2 Settings menu 2: Channel
You make the measuring channel settings in this menu (either individually or
for all channels simultaneously). Selecting a measuring channel:
1. Use the "" button to go to the measuring channel setting. Press "↵".
2. Use the UP/DOWN buttons to select a single measuring channel or all
measuring channels (1…12). Press "↵" to confirm your selection.
If the measuring channel settings only differ slightly, we
recommend to proceed as follows:
- First set all the channels (1…12) to the same value.
- Then modify the settings of individual channels.
Setting
a single
Setting
all measuring channels:
Chan.: 1
Exit
1.Resp.value:4mA
2.CT: W/WR
Chan.: 1..12
Exit
1.Resp.value:4mA
2.CT: W/WR
measuring channel: