Operation
57
EDS460-490_D00085_01_M_XXEN/02.2016
6.6.3.7 Settings menu 7: Alarm addresses
Setting of the bus addresses (1…150) externally connected to the BMS bus,
the alarm messages of which are to be displayed on this EDS…-D. Set the
addresses of devices whose messages are to be displayed to "on". Addresses
set to "on" are monitored for presence on the BMS bus; if a device cannot be
found on the bus, a corresponding message will appear. The address of this
EDS is set to "on" automatically.
on Messages of this device will be displayed.
off Messages of this device will not be displayed.
6.6.3.8 Settings menu 8: Clock
Set the date format, date, time, and summer time changeover.
1.Format
Set the German or American format.
d.m.y German format (day.month.year)
m-d-y American format (month-day-year)
2.Date
Set the date (e.g. 20.06.2010).
Set the time and date on the BMS bus master. All slaves
adopt this setting. The setting is synchronised every hour.
The "Clock" menu setting remain stored for approx. 2 h after
power supply failure.
Exit
1.Address: on
2.Address: off
3.Address: off