EasyManua.ls Logo

Bender EDS460 - Troubleshooting; Display Device Error

Bender EDS460
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Tests and service
66
EDS460-490_D00085_01_M_XXEN/02.2016
7.4 Troubleshooting
7.4.1 Display device error
An "error code" is displayed if a fault occurs. Please have this device information to
hand if you should need to contact us for assistance by telephone.
Display in the event of a fault
xx = Error code
Error
code
Description
1
Measurement technique: Fault parameter memory
(EEPROM/FLASH)
2 Measurement technique: Fault data memory (RAM)
4 Measurement technique: No boot loader available.
11 Measurement technique: Device not calibrated.
12
Measurement technique: Wrong measurement p.c.b., incor-
rect mounting
13
Measurement technique: Hardware error after performing a
self test
71
BMS interface: No master available resp. has not been que-
ried by a master for five minutes
72 BMS interface: Fault RS-485 interface
EDS…-D EDS…-L
Device error: xx Er
xx (alternately displayed)

Table of Contents

Other manuals for Bender EDS460