Data
70
EDS460-490_D00085_01_M_XXEN/02.2016
8.3 Technical data EDS460/490/EDS461/491
Insulation coordination acc. to IEC 60664-1/IEC 60664-3 for versions with a
supply voltage of AC/DC 70…276 V AC 42…460 Hz
Rated insulation voltage....................................................................................................................................AC 250 V
Rated impulse voltage/pollution degree.............................................................................................................6 kV/III
Protective separation (reinforced insulation) between................................. (A1, A2) - (k1, l…k12, R, T/R, T, A, B),
(C11, C12, C14), (C21, C22, C24), (11,14), (21,24), (31,34), (41,44), (51,54), (61,64), (71,74), (81,84), (91,94),
(101,104), (111,114), (121,124)
Protective separation (reinforced insulation) between.........................................(C11, C12, C14) - (C21, C22, C24) -
(11, 14, 21, 24, 31, 34) - (41, 44, 51, 54, 61, 64) - (71,74) - (81,84) - (91,94) - (101,104) - (111,114) - (121,124)
Dielectric test acc. to IEC 61010-1 ....................................................................................................................3.536 kV
Rated insulation voltage....................................................................................................................................AC 250 V
Rated impulse voltage/pollution degree.............................................................................................................4 kV/III
Basic insulation between: ..........................................k1, l…k12, R, T/R, T, A, B) - (C11, C12, C14), (C21, C22, C24)
Basic insulation between: ............................................. (11, 14) - (21, 24) - (31, 34) - (41, 44) - (51, 54) - (61, 64)
Voltage test acc. to IEC 61010-1 ........................................................................................................................2.21 kV
Insulation coordination acc. to IEC 60664-1/IEC 60664-3 for versions with a
supply voltage of DC 16…94 V, AC 42…460 Hz 16…72 V
Rated insulation voltage....................................................................................................................................AC 100 V
Rated impulse voltage/pollution degree..........................................................................................................2,5 kV/III
Protective separation (reinforced insulation) between.................................. (A1, A2) - (k1, l…k12, R, T/R, T, A, B)
Voltage test acc. to IEC 61010-1 ......................................................................................................................1.344 kV
Rated insulation voltage....................................................................................................................................AC 250 V
Rated impulse voltage/pollution degree.............................................................................................................4 kV/III
Basic insulation between:............................................................................... (A1, A2), (k1, l…k12, R, T/R, T, A, B) -
(C11, C12, C14), (C21, C22, C24), (11,14), (21,24), (31,34), (41,44), (51,54), (61,64), (71,74), (81,84),
(91,94),(101,104), (111,114), (121,124)
Basic insulation between: ............................................. (11, 14) - (21, 24) - (31, 34) - (41, 44) - (51, 54) - (61, 64)
Voltage test acc. to IEC 61010-1 ........................................................................................................................2.21 kV
Rated insulation voltage....................................................................................................................................AC 250 V
Rated impulse voltage/pollution degree.............................................................................................................6 kV/III