Tests and service
67
EDS460-490_D00085_01_M_XXEN/02.2016
7.4.2 Device error display (channel-related)
LED "Alarm 1" lights up. The common alarm relay switches. The EDS…-D dis-
plays:
Line 1: FAULT,
Alarm 1 of 1 pending alarm
Line 2: Alarm status and alarm text
No alarm
Alarm
Line 3: Error code (refer to „Display device error“ on page 66)
Line 4: BMS bus address of the EDS and the measuring channel on which the
alarm has occurred.
Possible causes:
Incorrect basic programming of the EDS.
Wrong p.c.b. assembly at four consecutive channels.
Internal memory fault.
Faulty channels after test.
Fault 1/1
Device error
11
Addr.:2 Chan.:4