Operation
38
EDS460-490_D00085_01_M_XXEN/02.2016
 EDS…-D: An alarm message is shown on the display.
Line 1: ALARM,
Alarm 1 of 1 pending alarm
Line 2: Alarm status and alarm text
No alarm
ALARM
Line 3: Currently measured mean value of the locating current.
Line 4: BMS bus address of the EDS and measuring channel on which the
alarm has occurred.
Press the "INFO" button to display the schematic representation for this
alarm message. Channels where an alarm exists are marked with the
symbol.
 EDS…-L: The alarm LED of the affected channel lights or flashes in case
of a device error.
ALARM 1/1
Insulation fault
12 mA
Addr.:2 Chan.:12
(
*
(
(
k 1 2 3 4 5 6 7 8 9
10
11
12
ISO fault location