Data from the digital outputs
Non-storing, current supplying (positive switching)
Protective circuit for
inductive loads
41 V terminal voltage
(typ.) compared to
+24 V
Fast de-excitation (must be provided externally)
One orange LED per output
Lights at logical 1
In the case of thermal overload, auto-resetting
Short circuit protection
response threshold
Electronic voltage limitation: typ. 7 A
The current is limited electronically. Activation of
short circuit protection results in thermal overload
and tripping of thermal overload protection.
Permissible limits based on cold state: max. 10,000
short circuits; overall duration max. 500 hours.
Status under unclear
operating conditions
If the supply voltage is insufficient, and at booting
up and shutting down the control system, the
outputs are set to logical 0.
Output delay “0” after
“1”
Output delay “1” after
“0”
Voltage drop (at rated
current)
Rated current at “1”
signal
Total current of all
outputs
Parallel circuit in two
outputs
Maximum permissible value with a logical
connection to increase power