Operating modes for the analogue inputs
Damage to channel
High voltages can damage analogue channels, stopping them from working
correctly.
Ensure the input voltage does not exceed ±30 V.
Operating mode: voltage input AI (U)
AI (U/T) and AGND or AI (U) and AGND;
connect screening with AGND.
Input impedance in
signal range
applies between AI (U/T) and AGND or
between AI (U) and AGND
value when the channel is switched on or off
Data format in
user program
(floating-point number) in millivolts (mV)
Maximum permissible
permanent overload
Max. ±30 V compared
to AGND
±30 V = max. voltage on AI channel
Value of least
significant bit
Output of digital value
in case of overload
If a voltage of ±10 V is applied to an AI (U), a
plausible value is still given up to approx. ±15 V.
The specified accuracy is only valid for the range
–10 to +10 V.
When applying voltages above +15 V or below
–15 V, a fault bit (FAULTN/FAULTP) is set in the
process image which can be read by the user
program..
Unsymmetrical voltage metering (single-ended)
Second-grade low-pass
filter; cut-off frequency
650 Hz