EasyManua.ls Logo

bioscrypt V-Flex 4G - Ground Fault Checks

bioscrypt V-Flex 4G
85 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
October152009InstallationGuideDraftEditPurposesOnly Page61
Installation Guide – October 2009 – Edit Purposes Only
2009
device Net-work IDs. Each device sharing a communication line must have a unique
device Network ID.
5.1.2 RS-232 TO RS-485 CONVERTER GROUND FAULT CHECK
Before a device can be connected to an RS-485 subsystem, it must be checked for
ground faults. An uncorrected ground fault can damage all devices connected to the
RS-485 communication line.
To check for a ground fault on the RS-232 to RS-485 converter:
3. Apply power to the RS-232 to RS-485 converter.
Connect the signal ground of the RS-485 line through a 10k ohm current-limiting resistor
to the signal ground of the RS-232 to RS-485 converter. There should be no more
than 1 volt across the resistor.
5.1.3 DEVICE GROUND FAULT CHECK
To check for a ground fault on a new V-Station 4G or V-Flex 4G device:
4. Apply power to all devices already successfully connected to the RS-485 line.
Power up the new device but do not connect it to the RS-485 line.
Connect the signal ground of the RS-485 line through a 10k ohm current-limiting resistor
to the signal ground of the V-Station 4G device.
There should be no more than 1 volt across the resistor. If there is, find and clear the
fault.
Repeat Steps 1 through 3 with each of the RS-485 signal lines (+ and -).
Connect the new device to the RS-485 line only if no ground fault is found.

Table of Contents