Security Functions
3–12
1070 073 822-104 (02.06) GB
Disable Auto Power Off
This option disables both the USP monitoring function and the power-off
delay for the power supply:
D A voltage interruption will cause the PC to shut down immediately.
D After a normal shutdown, the wait interval of approx. 60 seconds prior to
the shutdown of the power supply is omitted.
Although this function reduces the wait times during startups and software
installations, it must always be disabled during standard operation!
CAUTION
Loss of data!
Activation of this checkbox no longer makes a safe shutdown poss-
ible in the event of a power failure. The device switches off instantly!
Info
Shutdown Count
The displayed value shows how often the system was shut down by UPS, i.e.
how many charging cycles the battery has been subjected to. More details
regarding after how many charging cycles it is necessaary to replace the re-
chargebale batteries is contained in section 8.2.3.
Default button
Selecting this button returns all settings to their default values.
These are:
D COM port: COM4
D Shutdown Delay Time: 30 sek
D Enable Accu Test: enabled
D Enable Temp Control: enabled
D Disable Auto Power Off: disabled