Access Modular Controller 2 Troubleshooting | en 41
Bosch Security Systems B.V.
Installation manual
2021-04 | V04 | IM
7.2 Resetting the device to factory default
1. If connected to the Ethernet, release the connection.
2. Open the upper case of the controller as described in
Opening the case, page 16
.
3. Reset the controller as described in
Resetting the software, page 40
.
4. Set all six DIP switches of the RS-485 selector to ON (see figure below).
5. Press the reset button.
6. After completing this procedure, do not forget to set the DIP switches to your preferred
position (factory default 1 and 5 to ON).
Delivery status
Figure7.2: DIP switches
The controller now has the following network configuration:
DHCP = 1
IP = [assigned by DHCP server or “0.0.0.0” if not available]
Subnet mask = [assigned by DHCP server or “0.0.0.0” if not available]
Password = no password
Create your password in the IP Config settings of the AMC.

Other manuals for Bosch Access Modular Controller 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Access Modular Controller 2 and is the answer not in the manual?

Bosch Access Modular Controller 2 Specifications

General IconGeneral
BrandBosch
ModelAccess Modular Controller 2
CategoryController
LanguageEnglish

Related product manuals